Automated fault location scheme for low voltage smart distribution systems
Abstract
Integrating the self-healing capability realizes the automated protection of smart distribution systems. This article presents a fault location scheme for low voltage (LV) distribution systems based on the information collected from the smart meters. First, a fault condition is detected and classified by processing the current signal at the secondary side of the distribution transformer by an intelligent electronic device. Then, the faulty feeder and section are determined by calculating the fault-imposed component of nodal voltages. The reliable performance of the proposed scheme is verified through several case studies using a real semi-rural distribution system.
Introduction
Distribution systems are vulnerable to various faults, such as short circuits, overloads, and equipment failures, which can disrupt the power supply and pose significant risks to equipment and personnel. Thus, the protection of distribution systems is a critical aspect of ensuring the safe and reliable delivery of electricity to consumers. Traditionally, current-based protective devices such as overcurrent relays and fuses detect abnormal conditions and quickly isolate the faulty area to limit the fault impact and minimize downtime. However, locating the faults is a challenging task as they are located without any measurement, for example, by using the fuse and fault locator operation or relay targets [1]. It increases the average duration of interruptions experienced by customers served by the distribution system. According to the U.S. energy information administration report, the system average interruption duration index (SAIDI) for the U.S. distribution system in 2021 will be 475.8 and 125.7 min with and without considering major event days, respectively [2].
To improve the SAIDI, several fault location schemes are proposed in the literature [3, 4]. However, the vast majority of these schemes are presented for medium voltage (MV) distribution systems, and less attention is paid by researchers to developing fault location schemes for low voltage (LV) distribution systems with more complex structures and lower measurements. The complexity is due to the integration of single-phase loads and residential photovoltaic (PV) systems (imbalance), the presence of different types of conductors (heterogeneity), and the increased number of branches. These features degrade the performance of some MV fault location schemes; for example, the calculated distance by the impedance-based methods may determine multiple possible fault locations.
The fault location process of LV grids in many utilities is still based on customer phone calls. To automate this process, a few schemes are presented that can be categorized into three groups: i) learning-based, ii) reflectometry-based and iii) sparse measurements-based schemes. The first group of schemes use a learning method including gradient boosting trees [5], extreme gradient boosting [6], deep neural networks [7], and similarity criteria in the principal component subspace [8]. However, they suffer from the need for a training dataset. The second group schemes consist of injecting a high-frequency component and logging the line response [9], intelligent processing of time domain reflectometry by using very high sampling frequency equipment [10], and chaotic reflection measurement [11]. However, the performance of reflectometry-based schemes may determine multiple fault locations with an increased number of branches. The third group schemes use distributed measurements to locate a fault condition. In [12], current measurement units are installed at the head end of each branch to determine the amplitude and direction of the fault current. The current angle difference in two ends of feeder sections is the basis of the scheme presented in [13]. However, these schemes suffer from the need for current phasor measurement units (PMUs) that are not available in the LV distribution systems. With emerging smart distribution systems, advanced sensing, communication, and control technologies are integrated to enhance grid intelligence, flexibility, and reliability. The key components of smart grids such as smart meters, advanced sensors, and automation systems enable monitoring and data-driven decision-making, aiding to self-heal the smart distribution systems after the fault occurrence. By analyzing the voltage amplitude measurement by smart meters installed in feeder nodes, [14, 15] locate the fault. However, they suffer from disability in locating a fault in the first and last sectors of a feeder. Initiated by a customer phone call, a fault is located in [16] by using the status of receiving data from smart meters. However, it suffers from accurate faulty section identification in complex distribution systems and longer downtime due to dependency on customer phone calls. Moreover, except for the scheme in [13], none of the schemes of the three groups consider double-line and double-line to ground faults.
To address the limitations of third group schemes including the need for PMU, the inability to locate a fault in all sections of the feeder, the inability to locate a fault in a complex grid, and no evaluation for all types of fault, this article presents a fault location scheme for LV smart distribution systems based on the collected data from smart meters. In the first step, a fault condition is detected and classified based on the fault-imposed component of the secondary side current of the distribution transformer by an intelligent electronic device (IED). Then, the IED processes the collected voltage measurements from smart meters to determine the faulty feeder and section. The proposed fault location technique is based on the fault-imposed component of nodal voltages.
Proposed scheme
Figure 1 shows the single-line diagram of the study test system, which is a semi-rural three-phase four-wire LV distribution system [17]. It consists of three feeders and 33 nodes and includes three-phase, two-phase, and single-phase lines with various cable types and lengths. To capture the benefits of PV systems [18, 19], 18 single-phase residential PV units are integrated into the study system. These PV units, as well as 48 single-phase loads, are unsymmetrically distributed along the feeders. The study smart test system is equipped with 32 single- and multi-phase smart meters at all nodes for voltage measurement and one IED at the root node (node 1) for current measurement and data processing. The use of IED reduces the computational burden of the distribution system control center.

Fault detection and classification
To classify the fault, the phase current measurements are monitored. If the amplitude of the current in all phases increases, the fault is classified as a three-phase fault. If the amplitude of the current in one phase increases, it is classified as a single-phase-to-ground fault. In the case of increasing the amplitude of current in two phases, the fault-imposed component of zero-sequence current is monitored. A fault is classified as a double-line to ground fault if , where γ is the double-line classification threshold. Otherwise, it is classified as a double-line fault.
Fault location

It should be noted that according to the International Renewable Energy Agency (IRENA) grid code for renewable-powered systems [21], the low-voltage ride through (LVRT) capability is now required for distributed energy resources connected to low-voltage distribution systems to improve system reliability. However, there is no requirement for voltage support by injecting reactive power during LVRT events.
In addition, according to the EN 50160 standard [22], the permissible voltage drop in LV grids is 10% of the nominal voltage. It means that by using the limited measurement capability of available commercial smart meters, that is, voltage magnitude reports every 15 min, the detection of high-impedance faults (HIFs) is not possible as the voltage magnitude is inside the permissible range. However, since an IED is installed at the secondary side of the distribution transformer, an available HIF detection method such as those proposed in [23] can be integrated into the proposed scheme. Nevertheless, the detection of HIFs is out of the scope of this article.
Performance evaluation
To evaluate the performance of the proposed scheme, the study test system in Figure 1 is simulated in the MATLAB/Simulink environment. Several single- and multi-phase fault scenarios at different points of the feeder with various fault resistances and several no-fault scenarios including large load and PV switchings are conducted to determine thresholds of fault detection ξ and double-line classification γ; they are chosen to be 0.11 and 0.015 pu, respectively. The fault-imposed components should be calculated at the early stages of semi-steady-state conditions during the fault but before any operation of protective devices; in this article, the calculations are performed 150 ms after the fault occurrence [14]. Regarding the sampling frequency of 1 kHz of the IED, is chosen to be 150 samples. In the first case study, a solid double-line (a-b) fault occurs at sections 13–20 (the section between nodes 13 and 20) as a fault in the middle of a feeder. Table 1 presents the fault-imposed components of sequence and phase components of node 1 current as well as fault-imposed nodal voltages at phase b. The “—” line represents the lack of a smart meter at phase b in that node due to the absence of one (two) phase(s). exceed ξ and the fault is detected. Since only fault-imposed components of phases a and b exceed the threshold and there is no fault-imposed zero-sequence component, the fault is correctly classified as an a–b fault. Then, the IED processes the collected data from smart meters. The voltage magnitude of the smart meter at node 20 (SM20) has the highest . Thus, sections 13–20 are correctly determined to be the faulty section.
1.0509 | 0.8709 | 0.0006 | 1.2254 | 1.1955 | 0.0290 |
---|---|---|---|---|---|
Fault location index in phase B (pu) | |||||
Feeder 1 | Feeder 2 | Feeder 3 | |||
SM2 | 0.2135 | SM3 | 0.2785 | SM4 | 0.2201 |
SM5 | 0.2094 | SM6 | 0.2741 | SM8 | 0.2179 |
SM9 | 0.2069 | SM12 | 0.2594 | SM15 | 0.2152 |
SM16 | 0.2058 | SM19 | 0.2578 | SM23 | 0.2093 |
SM24 | 0.2047 | SM26 | 0.257 | SM28 | 0.1899 |
SM29 | 0.2031 | SM30 | — | SM32 | 0.1877 |
SM10 | 0.2049 | SM7 | 0.4532 | SM14 | 0.2161 |
SM11 | 0.2056 | SM13 | 0.4939 | SM22 | 0.2054 |
SM17 | — | SM20 | 0.5023 | ||
SM18 | 0.204 | SM27 | 0.5002 | ||
SM25 | 0.2026 | SM31 | 0.4927 | ||
SM33 | — | ||||
SM21 | 0.4763 |
- Abbreviations: PMU, phasor measurement unit; SM, smart meter.
In the next case study, a single-phase to ground fault (c-g) with a fault resistance of 1 Ω is simulated at sections 18–25 as a fault in the last section of a feeder. As presented in Table 2, the fault is correctly detected as a c-g fault as only exceeds the threshold. In addition, the voltage reported by SM25 has the highest change with respect to normal operation. Thus, sections 18–25 are determined as the faulty section.
0.1424 | 0.0339 | 0.0838 | 0.0418 | 0.0503 | 0.2048 |
---|---|---|---|---|---|
Fault location index in phase C (pu) | |||||
Feeder 1 | Feeder 2 | Feeder 3 | |||
SM2 | 0.0306 | SM3 | 0.0056 | SM4 | 0.0026 |
SM5 | 0.046 | SM6 | 0.0058 | SM8 | 0.0029 |
SM9 | 0.0458 | SM12 | 0.0065 | SM15 | 0.0031 |
SM16 | 0.0457 | SM19 | 0.0066 | SM23 | 0.0036 |
SM24 | 0.0455 | SM26 | 0.0066 | SM28 | 0.0045 |
SM29 | 0.0451 | SM30 | 0.0068 | SM32 | 0.0048 |
SM10 | — | SM7 | 0.0174 | SM14 | 0.003 |
SM11 | 0.1588 | SM13 | 0.0214 | SM22 | 0.0039 |
SM17 | — | SM20 | 0.0472 | ||
SM18 | 0.2092 | SM27 | 0.0629 | ||
SM25 | 0.2503 | SM31 | 0.0625 | ||
SM33 | 0.0623 | ||||
SM21 | — |
- Abbreviations: PMU, phasor measurement unit; SM, smart meter.
Depending on the class, the accuracy of smart meters is within or [24]. A solid three-phase fault is simulated at sections 1–4 as the first section of a feeder while the smart meter of node 2 as the faulty node has a −0.5% error. Table 3 presents the results. The real is 0.8584 pu which is reduced to 0.8541 pu due to the measurement error. Nevertheless, the faulty section is correctly determined as sections 1–4.
5.3745 | 0.0845 | 0.0091 | 3.8670 | 3.7697 | 3.7578 |
---|---|---|---|---|---|
Fault location index in phase A (pu) | |||||
Feeder 1 | Feeder 2 | Feeder 3 | |||
SM2 | 0.6389 | SM3 | 0.6496 | SM4 | 0.8541 |
SM5 | 0.6311 | SM6 | 0.6418 | SM8 | 0.8516 |
SM9 | 0.6266 | SM12 | 0.624 | SM15 | — |
SM16 | 0.6259 | SM19 | 0.6227 | SM23 | — |
SM24 | 0.6245 | SM26 | — | SM28 | — |
SM29 | 0.6192 | SM30 | — | SM32 | — |
SM10 | 0.628 | SM7 | 0.6384 | SM14 | 0.8324 |
SM11 | 0.6074 | SM13 | 0.6369 | SM22 | 0.7191 |
SM17 | 0.5879 | SM20 | 0.637 | ||
SM18 | — | SM27 | 0.6317 | ||
SM25 | — | SM31 | 0 | ||
SM33 | — | ||||
SM21 | — |
- Abbreviations: PMU, phasor measurement unit; SM, smart meter.
To evaluate the performance of the proposed scheme in the case of information loss, a double-line to ground (b-c-g) fault at sections 19–26 with fault resistance of 5 Ω is simulated while the data of node 26 is not received by the IED due to smart meter/communication failure. As presented in Table 4, the fault-imposed voltage of node 19 has the highest value, and the fault is located between nodes 12 and 19. Thus, the information loss results in one section error in locating the fault in this case. Moreover, the fault is classified as a double-line to ground fault as the zero-sequence current exceeds the double-line classification threshold γ.
0.1162 | 0.0228 | 0.0270 | 0.0472 | 0.1045 | 0.0937 |
---|---|---|---|---|---|
Fault location index in phase B (pu) | |||||
Feeder 1 | Feeder 2 | Feeder 3 | |||
SM2 | 0.0017 | SM3 | 0.0075 | SM4 | 0.0017 |
SM5 | 0.0017 | SM6 | 0.019 | SM8 | 0.0017 |
SM9 | 0.0018 | SM12 | 0.0634 | SM15 | 0.0017 |
SM16 | 0.0018 | SM19 | 0.0693 | SM23 | 0.0018 |
SM24 | 0.0018 | SM26 | LOST | SM28 | 0.002 |
SM29 | 0.0018 | SM30 | — | SM32 | 0.0021 |
SM10 | 0.0017 | SM7 | 0.0186 | SM14 | 0.0017 |
SM11 | 0.0018 | SM13 | 0.0223 | SM22 | 0.0019 |
SM17 | — | SM20 | 0.0471 | ||
SM18 | 0.0018 | SM27 | 0.0618 | ||
SM25 | 0.0018 | SM31 | 0.0607 | ||
SM33 | — | ||||
SM21 | 0.0216 |
- Abbreviations: PMU, phasor measurement unit; SM, smart meter.
Table 5 compares the features of the proposed fault location scheme with other sparse measurement-based schemes. Unlike [14, 15], the proposed scheme can locate a fault condition in the first and last sections of a feeder. Also, unlike [16], the proposed scheme can locate the faulty section in a complex distribution system. Moreover, unlike [12, 13], the proposed scheme does not require PMU. In addition, unlike most of these references, the performance of the proposed scheme is evaluated for all types of fault.
Conclusion
Based on the available voltage measurement by smart meters, this article presents a fault location scheme for a smart LV distribution system. The faulty feeder and section are located by calculating the fault-imposed component of nodal voltages using an IED installed at the root node of the grid. The IED also detects and classifies the fault by processing the current signal of the root node. The proposed scheme can locate all types of faults in all sections of a feeder, even in a complex distribution system, and without the need for the PMU. Several single- and multi-phase fault scenarios in an unbalanced heterogeneous distribution system demonstrate the proper performance of the proposed scheme even in the presence of measurement error up to 0.5% and information loss. Determination of faulty points along the section, accurate faulty section location in the case of information loss or a limited number of smart meters, and locating simultaneous faults and HIFs can be considered as the next step of this work.
Conflict of interest statement
The authors declare that there is no conflicts of interest.
Author contributions
Salar Naderi: Investigation; software; writing—original draft. Abbas Ketabi: Conceptualization; supervision; writing—review and editing. Iman Sadeghkhani: Conceptualization; methodology; supervision; visualization; writing—original draft.
Open Research
Data availability statement
Data sharing is not applicable to this article as no new data were created or analyzed in this study.